The Asphalt Roofing Manufacturers Association (ARMA) has established the following recommendations for applying asphalt shingles and/or asphalt-based underlayment directly over insulation, insulated roof decks, and radiant barriers.

Shingle Application Directly Over Insulation

Applying shingles directly over insulation is not recommended for a number of reasons.

  • Asphalt shingles and/or asphalt-based underlayments are designed for attachment to deck surfaces such as plywood and oriented strand board or other surfaces acceptable to the asphalt shingle or underlayment manufacturer
  • Continuous free-flow ventilation is impossible to achieve when applying shingles and asphalt-based underlayment directly over insulation. Heat build-up, a typical result of inadequate ventilation, may accelerate weathering and reduce the anticipated life of the products.
  • Asphalt shingles may be damaged or punctured when nailed onto a non-rigid surface such as roofing insulation.
  • Asphalt shingles and/or asphalt-based underlayment may be damaged or punctured when nailed onto a non-rigid surface such as roofing insulation.
  • Insulation does not have adequate nail-holding ability. Consequently, shingle damage and/or blow-off may occur if shingles are attached to insulation. Wind classification of the installed roofing system may be affected.

The fire classification of asphalt roofing products may be adversely affected when applied directly over insulation. Individual asphalt shingle and/or asphalt-based underlayment manufacturers should be consulted to determine the effects on such classifications. Fire classification installed roofing system may be affected.

Asphalt Shingle and/or Asphalt-based Underlayment Application Directly Over Insulated Roof Decks

Applying asphalt shingles and/or asphalt-based underlayment to insulated roof decks is not recommended unless the following factors are considered.

  • Direct installation over insulated roof decks is not recommended unless an adequate continuous ventilation space, free of obstructions, is provided between the top of the insulating material and the underside of an acceptable roof sheathing, Proper ventilation must be provided to dissipate heat and humidity build-up under the roof sheathing. More information on this can be found in ARMA’s technical bulletin, Ventilation and Moisture Control for Residential Roofing. Factors influencing the minimum ventilation requirement include type of construction, roof pitch/run, temperature, humidity, etc. Consult the deck manufacturer, deck system designer, and asphalt shingle/underlayment manufacturer for specific requirements.
  • Asphalt shingles and/or asphalt-based underlayment should only be fastened to deck surfaces such as plywood and oriented strand board or other surfaces acceptable to the asphalt shingle manufacturer.
  • Application of asphalt shingles and/or asphalt-based underlayment directly over insulated deck systems without providing adequate ventilation may affect the asphalt shingle and/or asphalt-based underlayment manufacturers’ product warranties. Consult individual product manufacturers for details and refer to local building codes.

Asphalt Shingle and/or Asphalt-based Underlayment Application over Deck Systems Containing Radiant Barriers

Applying asphalt shingles and/or asphalt-based underlayment over deck systems containing radiant barriers is at times acceptable, but several considerations should be noted.

  • Radiant barrier sheets that are fastened between or beneath the roof rafters should have proper ventilation between the radiant barrier and the decking so heat and humidity build-up can be dissipated.
  • Radiant barriers require a minimum 1-inch air space between the metallic surface and the next nearest surface. Otherwise, thermal conduction will override the reduction in radiant heat transfer. See the US Department of Energy’s bulletin on Radiant Barriers for more information (found here).
  • Radiant barriers installed directly beneath and in contact with the roof deck sheathing may interfere with proper deck ventilation. The asphalt shingle and/or asphalt-based underlayment manufacturers’ product warranties may be affected, so consult individual manufacturers for details. Refer to local building codes for specific project requirements that may apply.

Ventilation Considerations
Most vent system manufacturers recommend a soffit/ridge (inlet/outlet) venting ratio of between 50 and 60 percent. An air space of 3/4-inch (19 mm) is suggested as a minimum ventilation space; a 1.5-inch (38 mm) or wider space is preferred. Factors influencing this measurement include type of construction, roof pitch/run, temperature, humidity, etc. Larger roof expanses, such as those on commercial buildings, may require a much larger air space to move heat and moisture from the system because of their longer run. Adequate intake airflow must also be provided for proper ventilation dynamics. Consult the deck manufacturer, deck system designer, and asphalt shingle/underlayment manufacturer, as well as local building codes, for specific requirements. Some methods for creating a continuous air space for proper ventilation are shown in Figures A, B, and C (images found in the technical bulletin attached to this page).


*DISCLAIMER OF LIABILITY: This document was prepared by the Asphalt Roofing Manufacturers Association and is disseminated for informational purposes only. Nothing contained herein is intended to revoke or change the requirements or specifications of the individual roofing material manufacturers or local, state and federal building officials that have jurisdiction in your area. Any question, or inquiry, as to the requirements or specifications of a manufacturer, should be directed to the roofing manufacturer concerned. THE USER IS RESPONSIBLE FOR ASSURING COMPLIANCE WITH ALL APPLICABLE LAWS AND REGULATIONS.

Nothing contained herein shall be interpreted as a warranty by ARMA, either express or implied, including but not limited to the implied warranties of merchantability, fitness for a particular purpose or non-infringement. IN NO EVENT SHALL ARMA BE LIABLE FOR ANY DAMAGES WHATSOEVER, including special, indirect, consequential or incidental damages or damages for loss of profits, revenue, use or data, whether claimed in contract, tort or otherwise. Where exclusion of implied warranties is not allowed, ARMA’s liability shall be limited to the minimum scope and period permitted by law.